Nigeria’s electricity grid has recorded a total system collapse, the Transmission Company of Nigeria announced on Friday.
However, it swiftly stated that restoration of the grid was at an advanced stage and explained that the total collapse was due to tripping of three generator units at Egbin power generation station.
The daily report on Nigeria’s power sector that was made available to our correspondent by the transmission company on Friday in Abuja stated that the grid collapsed totally on Thursday, September 28, 2017, after the country generated 3,515 megawatts of electricity the preceding day.
The TCN said, “A total system collapse was recorded on September 28, 2017 at 20:03Hrs.
“Reports obtained from stations and the sequence of events generated by the SCADA system indicated that the system collapse was triggered by the tripping of Egbin Units ST4, ST6 and ST5 at ‘20:03:15, 20:03:32 and 20:03:34’ respectively.
“By this incident, the Nigerian electric power grid lost generation completely before restoration commenced at 20:22Hrs.”
The power transmission firm stated that a post-mortem analysis of the event indicated that grid generation was curtailed to about 4,262.7MW prior to the inception of the disturbance due to capacity under-utilisation, as the operational capability required to maintain grid stability had waned.
This, it said, left the system vulnerable to the extent that perturbations of this magnitude resulted in severe system frequency dip that culminated in system collapse.
Click to signup for FREE news updates, latest information and hottest gists everydayHowever, it swiftly stated that restoration of the grid was at an advanced stage and explained that the total collapse was due to tripping of three generator units at Egbin power generation station.
The daily report on Nigeria’s power sector that was made available to our correspondent by the transmission company on Friday in Abuja stated that the grid collapsed totally on Thursday, September 28, 2017, after the country generated 3,515 megawatts of electricity the preceding day.
The TCN said, “A total system collapse was recorded on September 28, 2017 at 20:03Hrs.
“Reports obtained from stations and the sequence of events generated by the SCADA system indicated that the system collapse was triggered by the tripping of Egbin Units ST4, ST6 and ST5 at ‘20:03:15, 20:03:32 and 20:03:34’ respectively.
“By this incident, the Nigerian electric power grid lost generation completely before restoration commenced at 20:22Hrs.”
The power transmission firm stated that a post-mortem analysis of the event indicated that grid generation was curtailed to about 4,262.7MW prior to the inception of the disturbance due to capacity under-utilisation, as the operational capability required to maintain grid stability had waned.
This, it said, left the system vulnerable to the extent that perturbations of this magnitude resulted in severe system frequency dip that culminated in system collapse.
Advertise on NigerianEye.com to reach thousands of our daily users
Where's Fashola? That's what I'm. asking.
ReplyDeleteWhat does Fashola know about electricity?
DeleteWhat did Jonathan just do now?there is God o
ReplyDeleteDid u see what PDP cause?
ReplyDeleteYes i can see they went with power in the swearing in of the new administration.
DeleteNo its the past administration lead by PDP GEJ,that went with the light since the resumption of the APC PMB lead administration since May 29,2015.
ReplyDeleteThe power failure is more than worst. Fashola,who never knew he will be minister for power criticized the past administration that any government that can not put power in place in six month is not fit to govern Nigeria. Today more than reverse is the case. Its going to 3years now of total black out. If its not militant that blew the gas lines its the past administration says ...Fashola..... as a party member i score APC Failure
This comment has been removed by a blog administrator.
ReplyDelete